Full- and Part-Load Performance Evaluation of a Variable Refrigerant Flow (VRF) System Using an Occupancy-Simulated Research Building
使用占用率模拟研究建筑对可变制冷剂流量(VRF)系统进行全负荷和部分负荷性能评估
Variable refrigerant flow (VRF) systems are touted for their superior part-load performance compared to conventional HVAC systems. A study was completed to evaluate the full and part-load performance of a VRF system compared with a conventional rooftop unit (RTU) variable air volume (VAV) system with electric resistance reheating in a multi-zone building with emulated occupancy. To accomplish this, full and part-load conditions (i.e., 100%, 75% and 50% loads) in the building were maintained alternately by conditioning either the entire building or selected zones, and emulating the occupancy, accordingly. To compare the performance of the two systems, each system was operated alternately for a weeklong period during which each of the three load conditions were maintained for 2-3 days, and the system parameters, indoor and outdoor conditions, loads, and energy use were monitored. This paper presents the cooling and heating season performance and energy use of both systems based on the monitored data during the summer of 2015 through winter of 2016. System performance is compared in terms of weather-normalized HVAC energy consumption and seasonal average COP. Based on the analysis, the energy savings for the VRF system compared with the RTU system for the cooling season are estimated to be 30%, 37%, and 47% under the 100%, 75%, and 50% load conditions, respectively. For heating season, the energy savings are 51%, 47% and 27% under the 100%, 75%, and 50% load conditions, respectively.