1.1
This practice covers a laboratory procedure by which an estimate may be made of the extent to which different coarse aggregates may polish.
1.2
The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard. Regarding sieves, per Specification
E11
: “The values stated in SI units shall be considered standard for the dimensions of the wire cloth openings and the diameter of the wires used in the wire cloth.” When sieve mesh sizes are referenced, the alternate inch-pound designations are provided for information purposes and enclosed in parentheses.
1.3
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.4
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
====== Significance And Use ======
4.1
This practice simulates the polishing action of vehicular traffic on coarse aggregates used in bituminous pavements.
4.2
A polish value is determined that may be used to rate or classify coarse aggregates for their ability to resist polishing under traffic.
Note 1:
The quality of the results produced by this standard are dependant upon the competence of the personnel performing the procedure and the capability, calibration, and the maintenance of the equipment used. Agencies that meet the criteria of Specification
D3666
are generally considered capable of competent and objective testing, sampling, inspection, etc. Users of this standard are cautioned that compliance with Specification
D3666
alone does not completely ensure reliable results. Reliable results depend on many factors: following the suggestions of Specification
D3666
or similar acceptable guideline provides a means of evaluating and controlling some of those factors.