Electric cables. Thermosetting insulated, armoured, fire-resistant cables of rated voltage 600/1 000 V for fixed installations, having low emission of smoke and corrosive gases when affected by fire. Specification
电缆 热固性绝缘铠装耐火电缆 额定电压600/1000 V 用于固定装置 受火灾影响时烟雾和腐蚀性气体排放量低 规格
发布日期:
2015-11-30
BS 7846:2015规定了混凝土结构和性能的要求
额定功率的热固性绝缘铠装耐火电缆
电压为600/1000 V,在以下情况下烟雾和腐蚀性气体排放量低:
受火灾影响。本英国标准适用于英国固定装置中使用的电缆
工业区、建筑物或类似应用,电力维护
火灾期间需要在规定的时间内供应。本英国标准规定了以下类型电缆的要求:两芯、三芯、四芯或四芯铠装和外护套电缆
五芯,带绞合铜导线;
多芯辅助电缆,钢丝铠装和外护套,带绞合电缆
铜导体。本英国标准根据电缆的特性规定了四类电缆
在分别评估耐火性和耐火性的试验中的性能
具有喷水和抗机械冲击火灾(F2类)和
通过直接机械冲击和水射流评估耐火性
组合(F30、F60和F120类)。本英国标准适用于设计最大使用寿命的电缆
导体持续温度为90°C,且最大短路
导线温度为250°C(最长5秒)。
注1:在某些情况下,可能会对电缆的温度施加限制
可能接触到或可能接触到其他材料的地方。注2:附录A给出了使用指南,附录B给出了铠装线试验,附录C
进行相容性试验,附件D进行磨损试验,附件E进行绝缘试验
外护套电阻常数试验,附录F给出了导体和
装甲,附录G给出了装甲的总横截面积,附录H给出了测试
外护套收缩率,附录I给出了F2类的耐火试验-
直径超过20 mm的电缆的附加规定,附录J给出
关于型式试验的说明。交叉引用:英国标准6387BS 7655-1.2BS 7655-1.3BS 7655-6.1BS 7671BS 8491BS EN 10244-2:2009BS EN 50363-5BS EN 50395BS EN 50396BS EN 60228BS EN 60229BS EN 60332-1-2:2004BS EN 60332-3-24:2009BS EN 60754-1BS EN 60811-501BS EN 60811-502BS EN 61034-2BS EN 62230IEC 60050-461BS 5099BS 7846:2009BS 8512BS 8519:2010BS EN 50265-5028BS EN-5028BS 614BS EN 6179BS EN 6002BS EN 614646BS EN 60046BS EN 614BS EN 614BS EN 61464646BS EN 600BS EN 600BS EN 612BS62275BS EN 62444IEC 60183取代了BS 7846:2009,该标准仍然有效。购买本文件时可获得的所有当前修订均包含在购买本文件中。
BS 7846:2015 specifies requirements for construction and performance of
thermosetting insulated, armoured, fire-resistant cables of rated
voltage 600/1 000 V having low emission of smoke and corrosive gases when
affected by fire.This British Standard is applicable to cables for use in fixed installations in
industrial areas, buildings or similar applications, where maintenance of power
supply during a fire is required for a defined period of time.This British Standard specifies requirements for the following types of cables:wire armoured and oversheathed cables with two-, three-, four- or
five-cores, and with stranded copper conductor;multicore auxiliary cables, wire armoured and oversheathed, with stranded
copper conductor.This British Standard specifies four categories of cables based on their
performance in tests which assess separately resistance to fire, resistance to fire
with water spray and resistance to fire with mechanical shock (Category F2) and
which assess resistance to fire with direct mechanical impact and water jet in
combination (Categories F30, F60 and F120).This British Standard is applicable to cables that are designed for a maximum
sustained conductor temperature of 90 °C and for a maximum short-circuit
conductor temperature of 250 °C (for a maximum of 5 s).NOTE 1 Limitation on the temperature of the cables might be imposed in situations
where they may be touched or where they could touch other materials.NOTE 2 Annex A gives the guide to use, Annex B gives armour wire tests, Annex C
gives compatibility test, Annex D gives abrasion test, Annex E gives insulation
resistance constant test on oversheath, Annex F gives resistance of conductor and
armour, Annex G gives gross cross-sectional area of armour, Annex H gives a test for
shrinkage of oversheath, Annex I gives the fire resistance test for category F2 -
additional provisions for cables with a diameter over 20 mm, and Annex J gives
notes on type tests.Cross References:BS 6387BS 7655-1.2BS 7655-1.3BS 7655-6.1BS 7671BS 8491BS EN 10244-2:2009BS EN 50363-5BS EN 50395BS EN 50396BS EN 60228BS EN 60229BS EN 60332-1-2:2004BS EN 60332-3-24:2009BS EN 60754-1BS EN 60811-501BS EN 60811-502BS EN 61034-2BS EN 62230IEC 60050-461BS 5099BS 7846:2009BS 8512BS 8519:2010BS 8573:2012BS EN 50265-2-1BS EN 50266-2-4BS EN 50356BS EN 50393BS EN 60079-14BS EN 61914BS EN 62275BS EN 62444IEC 60183Replaces BS 7846:2009 which remains current.All current amendments available at time of purchase are included with the purchase of this document.