1.1
This test method covers the determination of the dimensions and density, after conditioning, of preformed pipe insulation.
1.1.1
Procedure A is applicable to sections of one-piece pipe covering or to sections of segmental pipe covering that can be joined together concentrically and measured as one-piece.
1.1.2
Procedure B is applicable to segmental pipe covering where each section of material is measured.
1.1.3
Procedure C is applicable to sections of one-piece pipe covering, such as soft foam or mineral wool materials, where it is possible to penetrate the material.
1.2
The values stated in inch-pound units are to be regarded as the standard. The values given in parentheses are for information only.
1.3
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.4
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
====== Significance And Use ======
5.1
Density measurements of preformed pipe insulation are useful in determining compliance of a product with specification limits and in providing a relative gage of product weights. For any one kind of insulation some important physical and mechanical properties, such as thermal conductivity, heat capacity, strength, etc., bear a specific relationship with its density; however, on a density basis, these properties are not directly comparable with those for other kinds of material.
5.2
The physical dimensions of preformed pipe insulation are important quantities not only for determining the density of the pipe insulation but also for determining the conformance to specifications. The use of multilayer insulations is common, and the dimensions are necessary to ensure proper nesting of the layers.