This is a guide describing the surge voltage, surge current, and TOV environment in low-voltage [up to 1000 V root mean square (rms)] ac power circuits. This scope does not include other power disturbances, such as notches, sags, and noise. The surge considered in this guide do not exceed one-half period of the normal mains waveform (fundamental frequency) in duration. They can be periodic or random events and can appear in any combination of line, neutral, or grounding conductors. They include surges with amplitudes, durations, or rates of change sufficient to cause equipment damage or operational upset (see Figure ). While surge protective devices (SPDs) acting primarily on the amplitude of the voltage are often applied to divert the damaging surges, the upsetting surges may require other remedies. The rationale for including a description of TOVs in this guide on the surge environment is given in.