This document addresses environmental control within data centres based upon the criteria and
classifications for "availability", "security" and "energy efficiency enablement" within EN 50600-1.
This document specifies requirements and recommendations for the following:a) temperature control;b) fluid movement control;c) relative humidity control;d) particulate control;e) vibration;f) physical security of environmental control systems.
Safety and electromagnetic compatibility (EMC) requirements are outside the scope of this European
Standard and are covered by other standards and regulations. However, information given in this European
Standard may be of assistance in meeting these standards and regulations.Cross References:ISO 16890-1:2016EN 50600-2-2:2019BS EN 50600-2-2:2019EN ISO 16890-1:2016CLC/TR 50600-99-1EN 50600-1EN 62040-3EN 61439-1EN ISO 14644-8EN 50600-2-5ISO 14644-8EN 300 119-2ANSI/ISA 71.04-2013EN 50272-2EN 300 119-1ETS 300 019-1-3EN 300 119-3EN 50600-3-1EN 50600-2-1EN 300 119-5EN 50600-2-4EN 300 119-4IEC 60050-705:1995All current amendments available at time of purchase are included with the purchase of this document.