BS PD IEC/TS 60079-39:2015 specifies the construction, testing, installation and maintenance
of Power-i apparatus and systems which utilise electronically controlled spark duration
limitation to maintain an adequate level of intrinsic safety.This Technical Specification contains requirements for intrinsically safe apparatus and wiring
intended for use in explosive atmospheres and for associated apparatus intended for
connection to intrinsically safe circuits entering such atmospheres.This Technical Specification excludes the level of protection "ia" and the use of softwarecontrolled
circuits.This Technical Specification applies to electrical equipment utilising voltages not higher than
40 V d.c. and a safety factor 1,5 for Groups IIB, IIA, I and III. It is also applicable to Group IIC
"ic" apparatus with a safety factor 1,0. Group IIC "ib" apparatus with a safety factor 1,5 are
restricted to voltages up to 32 V d.c.This type of protection is applicable to electrical equipment in which the electrical circuits
themselves are incapable of causing an explosion of the surrounding explosive atmospheres.This Technical Specification is applicable to intrinsically safe apparatus and systems which
utilise electronically controlled spark duration limitation with the aim of providing more
electrical power while maintaining an adequate level of safety.This Technical Specification is also applicable to electrical equipment or parts of electrical
equipment located outside hazardous areas or protected by another type of protection listed
in the IEC 60079 series, where the intrinsic safety of the electrical circuits in explosive
atmospheres depends on the design and construction of such electrical equipment or parts of
such electrical equipment. The electrical circuits located in the hazardous area are evaluated
for use in such locations by applying this Technical Specification.This Technical Specification supplements and modifies the requirements of IEC 60079-0,
IEC 60079-11, IEC 60079-14, IEC 60079-17 and IEC 60079-25.Cross References:IEC 60079-0IEC 60079-11IEC 60079-14IEC 60079-25All current amendments available at time of purchase are included with the purchase of this document.