Thermal insulation products for building equipment and industrial installations. Factory made rigid polyurethane foam (PUR) and polyisocyanurate foam (PIR) products. Specification
建筑设备和工业装置用隔热产品 工厂生产的硬质聚氨酯泡沫塑料(PUR)和聚异氰脲酸酯泡沫塑料(PIR)产品 规格
发布日期:
2015-12-31
BS EN 14308:2015规定了工厂制硬质聚氨酯泡沫(PUR)的要求
和闭孔含量不低于90%的聚异氰脲酸酯泡沫(PIR)产品,或
无饰面,用于建筑设备和工业设备的隔热
工作温度范围约为-200°C至+200°C的装置。低于-50°C的工作温度,关于产品在环境中适用性的特殊试验
建议使用预期用途(例如氧气液化)。应注意制造商的建议
在所有情况下。产品以砌块、饰面板或未饰面板、管段、管段和预制件的形式制造。本欧洲标准描述了产品特性,包括测试程序,
合格性、标记和评价。本标准涵盖的产品也用于预制隔热系统和
复合板;不包括包含这些产品的系统的性能。本欧洲标准未规定应达到的给定财产的要求水平
通过一种产品来证明其在特定应用中的适用性。测试所需的水平
给定的应用可在法规和招标书中找到。在10°C下,宣称导热系数大于0100 W/(m·K)的产品不包括在
这是欧洲标准。本欧洲标准不包括现场绝缘(喷涂或分配)或
用于建筑结构隔热的产品。本欧洲标准不包括以下声学方面:直接空气传播声音
绝缘和冲击噪声传递指数。交叉引用:EN 822EN 823EN 824EN 825EN 826EN 1604EN 1609EN 12086EN 12667:2001EN 12939EN 13165EN 13172:2012EN 13467EN 13468EN 13471EN 13501-1:2007+A1:2009EN 13823EN 14706EN 14707EN 15715:2009EN ISO 4590ISO 4590ISO 8497EN ISO 8894ISO 8894-1EN ISO 9229:2007EN ISO 10456ISO 10456EN ISO 11925-2EN ISO 13787ISO 13787ISO 1608EN 120298EN 1208EN13469EN 13470EN 13471ISO 65第305/2011号法规(欧盟)购买本文件时提供的所有现行修订版均包含在购买本文件中。
BS EN 14308:2015 specifies the requirements for factory made rigid polyurethane foam (PUR)
and polyisocyanurate foam (PIR) products, with a closed cell content not less than 90 %, with or
without facings, which are used for the thermal insulation of building equipment and industrial
installations, with an operating temperature range of approximately, - 200 °C to + 200 °C.Below an operating temperature of - 50 °C, special tests regarding the suitability of the products in the
intended application are advised (e.g. liquefaction of oxygen). Manufacturer's advice should be heeded
in all cases.The products are manufactured in the form of blocks, faced or unfaced boards, pipe sections, segments and prefabricated ware.This European Standard describes product characteristics and includes procedures for testing,
evaluation of conformity, marking and labelling.Products covered by this standard are also used in prefabricated thermal insulating systems and
composite panels; the performance of systems incorporating these products is not covered.This European Standard does not specify the required level of a given property that should be achieved
by a product to demonstrate fitness for purpose in a particular application. The levels required for a
given application are to be found in regulations and invitations to tender.Products with a declared thermal conductivity greater than 0,100 W/(m·K) at 10 °C are not covered by
this European Standard.This European Standard does not cover products forin situ-insulation (spraying or dispensing) or
products for the insulation of the building structure.This European Standard does not cover the following acoustical aspects: direct airborne sound
insulation and impact noise transmission index.Cross References:EN 822EN 823EN 824EN 825EN 826EN 1604EN 1609EN 12086EN 12667:2001EN 12939EN 13165EN 13172:2012EN 13467EN 13468EN 13471EN 13501-1:2007+A1:2009EN 13823EN 14706EN 14707EN 15715:2009EN ISO 4590ISO 4590ISO 8497EN ISO 8894ISO 8894-1EN ISO 9229:2007ISO 9229:2007EN ISO 10456ISO 10456EN ISO 11925-2ISO 11925-2EN ISO 13787ISO 13787ASTM 3985EN 1602EN 1607EN 12089EN 12090EN 12429EN 13238EN 13469EN 13470EN 13471ISO 65Regulation (EU) No. 305/2011All current amendments available at time of purchase are included with the purchase of this document.