1.1
This specification establishes the requirements for welded copper tube for air conditioning and refrigeration service for use in connections, repairs, and alterations. The tube shall be made from one of the following coppers:
Copper UNS No.
Previously Used Designation
Type of Copper
C10100
OFE
Oxygen-free electronic
C10200
OF
Oxygen-free without-residual oxidants
C12000
DLP
Phosphorus-deoxidized, low-residual phosphorus
C12200
DHP
Phosphorus-deoxidized, high-residual phosphorus
Note 1:
Fittings used for soldered or brazed connections in air conditioning and refrigeration systems are described in ASME Standard B 16.22.
Note 2:
The assembly of copper tubular systems by soldering is described in Practice
B828
.
Note 3:
Solders for joining copper tubular systems by described in Specification
B32
. The requirements for acceptable fluxes for these systems are described in Specification
B813
.
1.2
Copper UNS No. C12200 shall be furnished, unless otherwise specified. The copper tube shall be supplied in annealed coils or drawn temper straight lengths.
1.3
Units—
The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.4
This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.
1.5
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.